Protection Control
Si39-504
88
Function
4.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against a malfunction or transient increase of discharge pipe temperature.
Each compressor performs the discharge pipe temperature protection control individually
in the following sequence.
[INV compressor]
[STD compressor]
In discharge pipe temp.
protection control
HTdi>115˚C
Tp>140˚C
HTdi :Value of INV compressor discharge pipe
temperature (Tdi) compensated with
outdoor air temperature
Tp :
Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
or
Normal operation
INV upper limit frequency:
1-step down from current
compressor frequency
INV upper limit frequency: 1-step up
from current compressor frequency
RXYQ5MA: 52Hz
Other models:
INV62 Hz + OFF + OFF
HTdi>115˚C
Tp>140˚C
or
Every 30 sec.
HTdi>135˚C
HTdi>120˚C for 10 min. or more.
or
HTdi<110˚C
Tp<125˚C
&
Every 60 sec.
HTdi>130˚C
HTdi>120˚C
for 90 sec.
or more.
Tp>130˚C
or
HTdi<100˚C
Tp<110˚C
&
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
Discharge pipe
temperature standby (for
a period of 10 minutes)
• HTds>120˚C continues for 5 min. or more.
• HTds>135˚C
• Tp>140˚C continues for 10 min. or more.
• Tp>150˚C
or
Applicable STD
compressor stops.
10 min.
Discharge pipe temp.
protection control not limited
HTds : Value of STD compressor discharge
pipe temperature (
Tds) compensated
with outdoor air temperature
Tp:
Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...