Si39-504
Troubleshooting (OP: Schedule Timer)
Troubleshooting
241
5.3
“
M8
”
Malfunction of Transmission Between Optional
Controllers for Centralized Control
Remote
Controller
Display
M8
Applicable
Models
Schedule timer
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data. (The system will be
automatically reset.)
Malfunction
Decision
Conditions
When no master controller is present at the time of the startup of slave controller.
When the optional controllers for centralized control which was connected once, shows no
response.
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control
Defect of PC board of optional controllers for centralized control
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2838)
Is
transmission wiring
disconnected or wired
incorrectly?
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
NO
NO
Fix the wiring correctly.
YES
YES
Has a
once connected
optional controller for
centralized control been
disconnected or
its address
changed?
Turn on power supply for all
optional controllers for centralized
control.
Reset power supply
simultaneously for all optional
controllers for centralized control.
YES
NO
Is
the power supply
turned on for all optional
controllers for
centralized
control?
Set reset switch to "normal".
YES
NO
Is
the reset switch
of all optional controllers
for centralized control
set to "normal" ?
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...