SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
302
3.35 Activation of High Pressure Switch
Applicable
Models
All outdoor unit models
Error Code
E3
Method of Error
Detection
Detect continuity across the high pressure switch in the protection device circuit.
Error Decision
Conditions
When part of the protection device circuit opens.
(Reference) Operating pressure of the high pressure switch:
Operating pressure: 4.0 MPa (580 psi)
Resetting pressure: 3.0 MPa (435 psi)
Supposed
Causes
Activation of high pressure switch
Defective high pressure switch
Defective outdoor unit main PCB (A1P)
Momentary power failure
Defective high pressure sensor
Troubleshooting
NO
YES
YES
Replace the high pressure
switch (S1PH, S2PH).
Remedy defective points.
YES
Are the
above 3 points
OK?
Does the error
E3
recur?
NO
Is the
operating
pressure of the high
pressure switch
normal (4.0 MPa
(580 psi))?
NO
(1) Mount a pressure gauge on the high pressure
service port.
(2) Reset the operation using the remote controller,
and then restart the operation.
A
Check for the following 3 points:
(1) Is the stop valve open?
(2) Is the high pressure switch connector properly
connected to the outdoor unit main PCB?
(3) Is there continuity across the high pressure switch?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Go to the next page.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...