![Daikin VRV EMERION RXYQ-AATJA Service Manual Download Page 307](http://html2.mh-extra.com/html/daikin/vrv-emerion-rxyq-aatja/vrv-emerion-rxyq-aatja_service-manual_4706199307.webp)
SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
300
3.33 Detection of Ground Leakage by Leak Detection Circuit
Applicable
Models
All outdoor unit models
Error Code
E2
Sub code: 01, 02
Method of Error
Detection
Detect leakage current in the ground leakage detection circuit and detect error on the outdoor unit
main PCB.
Error Decision
Conditions
The leakage current is detected.
Supposed
Causes
Ground fault
Improper wiring passing through the current sensor
Temporary liquid compression or melting in compressor
Troubleshooting
YES
NO
NO
Is wiring
passing through the
current sensor (T1A)
proper?
Insulation failure of
compressor
Insulation failure of
component except
compressor
Pass proper wiring through the
sensor.
Turn OFF the power supply,
and then disconnect
compressor lead wire.
Reinstall wiring, and then turn
ON the power supply again.
NO
Replace the compressor.
YES
Replace the relevant
component.
YES
Normal (Continue operation)
The error is considered to have
resulted from temporary liquid
compression or penetration in
the compressor.
Take care of the liquid when
power is shut down over an
extended period of time due
to power failure or else.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...