Troubleshooting by Error Code
SiUS342303E
299
Part 6 Service Diagnosis
3.32 Outdoor Unit Main/Sub PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
E1
Method of Error
Detection
Abnormality is detected under the communication conditions in the hardware section between the
indoor unit and outdoor unit.
Error Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal.
Supposed
Causes
Defective outdoor unit main PCB (A1P)
Defective outdoor unit sub PCB (A8P)
Defective connection communication line between indoor and outdoor units
Troubleshooting
Return to normal?
YES
External factor other than error (for
example, noise etc.).
Connect the communication line
correctly.
Replace the outdoor unit main PCB
(A1P).
NO
NO
Check if
inside/outdoor relay
wires of outdoor unit main/sub
PCB is disconnected.
YES
Turn OFF the power once
and turn ON again.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Does the error
code show E1-08/09?
NO
YES
Replace the outdoor unit sub PCB
(A8P).
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...