Troubleshooting by Error Code
Part 6 Service Diagnosis
260
3.9 Overload/Overcurrent/Lock of Indoor Fan Motor
Applicable
Models
FXMQ-M
Error Code
A6
Outline
This error is detected by detecting that the individual power supply for the fan turns OFF.
Error Decision
Conditions
When it is not detected that the individual power supply for the indoor fan turns ON while in
operation.
Supposed
Causes
Defective power supply for the indoor fan motor
Clogged drain piping
Activation of the indoor unit safety device
Defective contact in the fan wiring circuit
Troubleshooting
Properly connect the ca
b
le.
NO
YES
YES
Is the
power s
u
pply
ca
b
le of the indoor fan
properly
connected?
NO
Is the fan
normally r
u
nning?
Restart the fan.
Replace the indoor
u
nit control
PCB (A1P).
It is s
u
pposed that the indoor
fan motor (M1F, M2F) stops
r
u
nning d
u
e to o
v
erload,
o
v
erc
u
rrent, or lock.
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...