SiUS342303E
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
210
2.5 Night-Time Low Noise Operation and Demand Operation
2.5.1 Night-Time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external control
adaptor (optional), you can lower operating noise.
A. When night-time low noise operation is carried out by external contact (with the use of
the external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short circuit terminal of night-time low
noise operation (Refer below figure). If carrying out demand or low noise input, connect the
adaptor’s terminals as shown below.
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select an external low noise level for the item 2-25.
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON.
(If the condition is set to ON, when the air conditioning load reaches a high level, the low noise
operation command will be ignored to put the system into normal operation mode.)
B. When night-time low noise operation is carried out automatically. (External control
adaptor for outdoor unit is not required.)
1. While in setting mode 2, select a night-time low noise operation level for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 6:00 AM, 7:00 AM, or 8:00 AM) for the item 2-27. (Use the ending time as a guide since it
is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON.
(If the condition is set to ON, when the air conditioning load reaches a high level, the system will
be put into normal operation mode even during night-time.)
Setting
Content
Level 1
Set the outdoor fan to Step 7 or lower.
Level 2
Set the outdoor fan to Step 6 or lower.
Level 3
Set the outdoor fan to Step 5 or lower.
Outdoor wiring indicated
by dotted line
External control
adaptor for outdoor unit
Host computer monitor
panel or demand controller
X
X
X
X
X
X
X
X
1
2
3
C
Demand
Low
noise
F1
F2
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...