Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
170
1.4.17 Thermostat Switching
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
1.4.18 Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
When thermostat OFF airflow volume up mode is used, careful consideration is required before
deciding installation location.
: Factory setting
1.4.19 Setting of Operation Mode to AUTO
This setting makes it possible to change differential values for mode selection while in automatic
operation mode, only when the wireless remote controller or any central remote controller is
connected.
: Factory setting
The automatic operation mode setting is made by the use of the "Operation Mode Selector" button.
1.4.20 Auto Restart after Power Failure
: Factory setting
When the "Auto Restart after Power Failure" setting is turned OFF, all the units will remain OFF
after power failure, or after the main power supply is restored. When this setting is turned ON
(factory setting), the units that were operating before the power failure will automatically restart
operation after power failure, or after the main power supply is restored.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Model
Second Code No.
Contents
FXFQ-T, FXEQ-P, FXHQ-M, FXTQ-TA
01
1°C (1.8°F)
FXZQ-TB, FXUQ-PA, FXDQ-M, FXSQ-TB, FXMQ-PB,
FXMQ-TB, FXMQ-M, FXAQ-P, FXLQ-M, FXNQ-M, FXMQ-MF,
CXTQ-TA
02
0.5°C (0.9°F)
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code
No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
(0°F)
1°C
(1.8°F)
2°C
(3.6°F)
3°C
(5.4°F)
4°C
(7.2°F)
5°C
(9.0°F)
6°C
(10.8°F)
7°C
(12.6°F)
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
5
01
OFF
02
ON
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...