Field Settings for Indoor Unit
SiUS342303E
163
Part 5 Field Settings and Test Operation
Note(s)
: Factory setting
When the 10 (20)-6 setting is changed to
02
, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.4.3 Filter Cleaning Sign
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
: Factory setting
Filter cleaning sign is not displayed when an Auto-clean Panel is connected.
1.4.4 Information for intelligent Touch Manager/intelligent Touch Controller
: Factory setting
When field setting 10 (20)-6-
02
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10
(20)-2 has priority.
When field setting 10 (20)-6-
01
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10 (20)-6
has priority for group connection, and 10 (20)-2 has priority for individual connection.
1.4.5 Time for Absence Area Detection (For units with an infrared presence
sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time. Absent time defined for detection can be selected as follows:
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
10 (20)
6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
5
01
Only indoor unit sensor value (or remote controller sensor
value, if installed.)
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...