Outline of Control (Indoor Unit)
SiUS342303E
135
Part 4 Functions and Control
9.7 Freeze-Up Prevention Control
When the temperature detected by the liquid pipe temperature thermistor of the indoor heat
exchanger drops too low, the unit enters freeze-up prevention control in accordance with the
following conditions, and is also set in accordance with the conditions given below. (Thermostat
OFF)
When freeze-up prevention is activated, the electronic expansion valve is closed, the drain pump
turns on and the airflow rate is fixed to L tap. When the following conditions for cancelling are
satisfied, it will reset.
Conditions for starting:
Liquid pipe temperature
≤
– 1°C (30.2°F) (for total of 40 minutes)
or
Liquid pipe temperature
≤
– 5°C (23°F) (for total of 10 minutes)
Condition for cancelling:
Liquid pipe temperature
≥
+7°C (44.6°F) (for 10 minutes continuously)
Concept of freeze-up prevention control
System avoids freeze-up
· For comfort, system avoids unnecessary thermostat ON/OFF
· For ensuring compressor reliability, system avoids unnecessary compressor ON/OFF
When freeze-up prevention control starts, system makes sure the frost is completely removed.
· System avoids water leakage.
Freeze-Up Prevention by Off Cycle (Indoor Unit)
N
ormal operation
Start
Cancel
Liquid pipe
temperature
Start
Cancel
N
ormal operation
–
5
ºC
(23˚F)
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
–
1
ºC
(30.2˚F)
t1
t2
t3
t4
0
ºC
(32˚F)
+
7
ºC
(44.6˚F)
10 min.
OR
10 min.
10 min.
t
>
40
minutes
Freeze-up prevention control
Forced OFF by thermostat
Freeze-up prevention control
Forced OFF by thermostat
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...