SiUS341802EC
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
152
Note(s)
Note(s)
The control is automatically switched to the one performed only by the suction air thermistor for
indoor unit when the Second code No. is
01
during group control.
To use the
remote controller thermistor control during group control
, select the Second code
No.
02
in First code No.
6
.
: Factory setting
When the 10 (20)-6 setting is changed to
02
, several indoor units are controlled by one remote
controller thermistor, so note that the room temperature might be uneven.
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
Filter cleaning sign is not displayed when a self-cleaning decoration panel is mounted.
1.4.4 Information for intelligent Touch Manager/intelligent Touch Controller
: Factory setting
When field setting 10 (20)-6-
02
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10
(20)-2 has priority.
When field setting 10 (20)-6-
01
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10 (20)-6
has priority for group connection, and 10 (20)-2 has priority for individual connection.
1.4.5 Time for Absence Area Detection (For units with an infrared presence
sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to
the energy-saving end by 1°C (1.8°F) (maximum 2°C (3.6°F)) after the state of absence continues
for a certain period of time. Absent time defined for detection can be selected as follows:
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
10 (20)
6
01
Remote controller thermistor control is not permitted during
group control
02
Remote controller thermistor control is permitted during group
control.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
5
01
Only indoor unit sensor value (or remote controller sensor
value, if installed.)
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
Summary of Contents for VRV Aurora RXLQ-TATJU Series
Page 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Page 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Page 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Page 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Page 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...