Troubleshooting by Remote Controller
Si71-812
54
Troubleshooting
1. Troubleshooting by Remote Controller
1.1
The INSPECTION / TEST Button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Normal
mode
Inspection
mode
Test
operation
mode
Local
setting
mode
Service
mode
Depress Inspection/Test Operation button
for more than 4 seconds.
Depress Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes
After 10 seconds
Press Inspection/Test Operation
button once.
Press Inspection/Test Operation
button once.
Indoor unit settings can be made
• Filter sign time
• Air flow direction
• Others
Following codes can be checked.
• Malfunction codes
• Indoor model code
• Outdoor model code
Service data can be obtained.
• Malfunciton code history
• Temperature data of various sections
Service settings can be made.
• Forced fan ON
• Air flow direction/volume setting
Thermostat is forcibly turned on.
(V0815)
Summary of Contents for VKM50GAV1
Page 9: ...Introduction Si71 812 viii...
Page 43: ...Operation Si71 812 34 Operation...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Page 103: ...Piping Diagram Si71 812 94 Appendix...
Page 105: ...Si71 812 ii Index...