Control Functions
Si71-812
50
Control Functions
1.1.5 Air Conditioner Link Operation
Link system enables simultaneous ON/OFF operation of heat reclaim ventilation unit and air
conditioner (VRV system, Skyair).
1) 1 group link control
Allows simultaneous ON/OFF from remote controller for air conditioner.
Allows independent operation of heat reclaim ventilation unit from VRV-system remote
controller during interim periods (not possible when direct duct connection is used).
ON/OFF operation is not possible from LCD remote controller of heat reclaim ventilation unit.
2) Link control of 2 or more groups (zone link)
Heat reclaim ventilation unit can be operated when one or more air conditioners are
operating.
Allows independent operation of heat reclaim ventilation unit from VRV-system remote
controller during interim periods (direct duct connection is not allowed in this system).
ON/OFF operation is not possible from LCD remote controller of heat reclaim ventilation unit.
Note:
With Super Wiring, units of different outdoor systems can be linked in operation.
VRV system
(HL024)
Remote
controller for
air conditioner
LCD
remote controller
for heat reclaim
ventilation unit
Group
1
Group
2
(HL025)
Group
3
Adapter PCB
for remote control
(KPR2A61)
Remote controller
for air conditioner
Remote controller
for air conditioner
Remote controller
for air conditioner
Summary of Contents for VKM50GAV1
Page 9: ...Introduction Si71 812 viii...
Page 43: ...Operation Si71 812 34 Operation...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Page 103: ...Piping Diagram Si71 812 94 Appendix...
Page 105: ...Si71 812 ii Index...