Si71-812
Operation
Opration
17
1.3
Central Control System
•
When carrying out a central connection, connect the central line to F1 and F2 only on the corresponding
VRV indoor unit’s PC-board. Do not connect to F1 and F2 on the ventilation side. ( = Connect to the
terminal block X3M.)
An image sketch of internal wiring on the ventilation side
•
In case of a central control, operation ON/OFF can be done separately by each zone. (In this case, zone
interlocked setting must be kept as the factory setting (17.08.01).)
•
Structure without a remote controller cannot be accepted because the remote controller group is
controlled within a VKM-GA(M) model. (i-Touch controller, central remote controller)
Connection to central
line is prohibited.
Remote controller
for air-conditioner
Ventilation PC-board
Corresponding VRV
indoor unit’s
PC-board
JC
J2
T1
T2
Note 1)
Centralized units
F1
F2
P1 P2
F1
F2
P1 P2
F1
F2
P2
P1
A1P
A2P
Terminal block X3M
* Alteration of set temperature and independent ventilation operation cannot be performed from a central device.
Group interlock zone setting : None
Zone interlock setting : None
Without a remote controller
Summary of Contents for VKM50GAV1
Page 9: ...Introduction Si71 812 viii...
Page 43: ...Operation Si71 812 34 Operation...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Page 103: ...Piping Diagram Si71 812 94 Appendix...
Page 105: ...Si71 812 ii Index...