250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415946-1 – 2015.08
Installation manual
2
D
IMENSIONS
(See
)
I
NSTALLATION
Installation position
■
Example of Installation (See
)
1
Maintenance space for the heat exchange elements, air filters and
fans
2
Maintenance cover
3
Inspection hole
■
450 mm
4
Switch box
5
4x 14x40 mm Ceiling hook (Oval hole)
6
Exhaust air fan
7
OA (Outdoor air) Fresh air from outdoors
8
EA (Exhaust air) Exhaust air to outdoors
9
Supply air fan
10
SA (Supply air) Supply air to room
11
RA (Return air) Return air from room
12
Damper plate
13
Heat exchange elements
14
Air filters
15
Applicable duct
16
Nominal diameter
CAUTION
■
The appliance is designed to be a built-in
appliance. It shall not be accessible to the general
public. Adequate measures have to be taken to
prevent access by other than qualified persons.
■
Install the unit in a place strong enough to
support its weight.
Poor installation is hazardous. It also causes
vibrations and unusual operating noise.
■
Provide the service space and the inspection
holes.
(Be sure to provide the inspection holes to inspect the
air filters, the heat exchange elements and fans.)
■
Do not install the unit directly against a ceiling or
wall.
(If the unit is in contact with the ceiling or wall, it can
cause vibration.)
■
This is a class A product. In a domestic
environment this product may cause radio
interference in which case the user may be
required to take adequate measures.
1
Air suction/discharge grille (option)
2
Inspection hole
■
450 mm (field supply)
3
Maintenance space for the heat exchange elements, air filters and
fans
4
Duct (field supply)
5
Duct (Ø200) (field supply) or (*) Flexible duct (option)
6
Branch duct (field supply) (only for VAM800~2000F)
7
(*) Flexible duct (option)
8
(*) Silencer (option)
9
EA (Exhaust air to outdoors)
10
Heat Insulator (field supply)
11
OA (Outdoor air) Fresh air from outdoors
12
Metal suspension bracket for absorbing vibration (field supply)
13
Suspension bolt (field supply)
14
Gradient of down to outdoor
≥
1/50
15
SA (Supply air to room)
16
RA (Return air from room)
17
Round hood (field supply)
18
Suspension bolt position
19
Additional external damper (field supply)
CAUTIONS
on installing the ducts
■
The parts marked with (*) are effective in reducing
blowing noise.
■
When using the unit at a quiet place, use the optional
silencer box and flexible duct at the part of the air
discharge outlet on the indoor side "SA" (supply air to
room) of the unit, to counter the noise.
■
When selecting installation materials, consider the
required volume of air flow and noise level in that
particular installation.
■
When the outdoor air infiltrates into the ceiling and the
temperature and humidity in the ceiling become high,
insulate the metal portions of the unit.
■
Access inside the unit is only allowed through the
service hole. Install grilles in case no ducts are
installed.
■
Unit sound pressure level is less than 70 dB(A).
Summary of Contents for VAM250FC
Page 22: ...NOTES...
Page 23: ...NOTES...