Si-93
Troubleshooting
Troubleshooting
33
1.3
Overall Malfunction
Remote Controller
LCD Display
Error Code
666
6000
0
Inspection
5
Unit No.
5
LED Indication
Remote Controller
5
Main Unit
5
Error Detection
Method
Errors are detected based on open circuit in external input terminals (J1-JC).
Error Generating
Conditions
When external input terminal (J1-JC) is shorted during operation (“Overall Alarm” must be set in field
setting mode).
Possible Causes
■
Faulty external device
■
Broken wire
■
Faulty control PCB
Troubleshooting
Measure resistance
between external
input terminals
(J1-JC).
Is
resistance
200
Ω
or
lower?
YES
YES
Remove the cause of error in
connected external device.
Check wires for abnormalities
(broken wire, faulty contact,
etc.).
Replace control PCB.
Is
connected
external device
operating
properly?
NO
(HF002)
NO
Summary of Contents for VAM 500EJ
Page 5: ...Si 93 iv Table of Contents...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning...
Page 8: ...Si 93 Introduction vii...
Page 11: ...Si 93 2 General Constructions...
Page 15: ...Si 93 6 Operation...
Page 21: ...Si 93 12 Maintenance...
Page 27: ...Si 93 18 Control Functions...
Page 35: ...Si 93 26 Circuit Operations...
Page 39: ...Si 93 30 Troubleshooting...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting...
Page 61: ...Si 93 52 Supplementary Explanation...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65...
Page 73: ...Si 93 64 Appendix...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE...
Page 79: ...Si 93 iv Index...