SiE71-202
Control Functions
Control Functions
27
1.3
Layout of switches on Printed Circuit Board
1.3.1
Printed Circuit Board
1.3.2
Function of main connection terminal
Secondary
Primary
Dumper
Exhaust
air fan
Supply
air fan
REMOTE
CONTROLLER
CENTRAIZD
CONTROL
THE INPUT
FROM OUTSIDE
Outdoor
Thermistor
Indoor
Thermistor
Dumper 1
Dumper 2
For
KRP50-2
Power supply
Factory setting
Be sure to give
the electric
grounding (earth)
connection.
CN3
CN4
CN2
CN1
CN7
FuL
10A
CN13
CN8
CN12
CN5
CN6
CN9
KRP
50-2
SS1
CN11
CN10
L
N
L
N
H
M
L
P2
P1
F1
F2
J1
J2
JC
P2
P1
F1
F2
J1
J2
JC
SS1
H
M
L
Dumper
*: VAM1500FJVE and VAM2000FJVE only
(HC0110)
3P034928-2B
Terminal No.
Contents of function
Single phase 220 – 240 V 50Hz
Single phase 220 – 220 V 60Hz
Power supply and earth terminal
Connection terminal for remote controller for HRV
unit.
This terminal is used to receive information of the
indoor unit for interlocked operation.
This terminal is used to receive information when
centralized controller is connected.
Between terminal no. (J1) ~ (JC)
Used for “fresh up operation” by external input.
Between terminal no. (J2) ~ (JC)
Used for Operation / Stop by external input.
Power supply
Remote controller
Centralized control
Input from outside
J1 J2 JC
P1 P2
L N
TeS1
F1 F2
(HC0043)
Summary of Contents for VAM 150FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...