SiE71-202
Troubleshooting
Troubleshooting
51
1.18
Power Transformer
Error Detection
Method
Check resistance and voltage with tester, and insulation resistance with megger.
Error Generating
Conditions
Possible Causes
Troubleshooting
Resistance of primary side of transformer: approx. 140
Ω
Resistance of secondary side of transformer: approx. 1.9
Ω
Voltage at secondary side of transformer when rated voltage is applied to primary side: approx. 26 VAC
Insulation resistance between primary side of transformer and case: 100 M
Ω
or higher
Insulation resistance between secondary side of transformer and case: 100 M
Ω
or higher
Insulation resistance between primary side and secondary side of transformer: 100 M
Ω
or higher
Check resistance of
primary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Check resistance of
secondary side of
transformer.
Does
measured
resistance
deviate significantly
from values
shown
below?
YES
NO
Apply rated voltage to
primary side of
transformer, and check
output voltage of
secondary side
of transformer.
Does
measured
voltage deviate
significantly from
values shown
below?
YES
NO
Transformer is faulty.
Transformer is faulty.
Transformer is faulty.
Transformer is normal
(HF016)
(HL037)
Check resistance and voltage
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...