Control Functions
SiE71-202
24
Control Functions
2) Link control of 2 or more groups (zone link)
Heat recovery ventilation unit can be operated when one or more air conditioners are operating.
Allows independent operation of heat recovery ventilation unit from VRV-system remote controller
during interim periods (direct duct connection is not allowed in this system).
ON/OFF operation is not possible from LCD remote controller of heat recovery ventilation unit.
Note:
With Super Wiring, units of different outdoor systems can be linked in operation.
1.2.5
Field Setting, Service Mode
1. Field setting
Used for initial setting of heat recovery ventilation unit.
2. Service mode
Used for confirmation of unit Nos. in the group and reallocation of unit Nos.
List of Field Setting and Service Mode
Group
1
Group
2
(HL025)
Group
3
Adapter PCB
for remote control
(KPR2A61)
Remote controller
for air conditioner
Remote controller
for air conditioner
Remote controller
for air conditioner
Details of setting
Mode
Setting
mode
Setting
switch
No.
Setting position
Operation method
01
02
03
04
05
06
Group No. setting
for centralized
controller
(individual)
Field
setting
00(30)
Filter cleaning
time setting
17(27)
0
Approx.
2500 hr.
Approx.
1250 hr.
No counting
—
—
—
Pre-cool/pre-heat
On/Off setting
2
Off
On
—
—
—
—
Pre-cool/pre-heat
time (min.)
setting
3
30 min.
45 min.
60 min.
—
—
Fan speed initial
setting
4
Normal
Ultra-High
—
—
—
—
Yes / No setting
for direct duct
Connection with
VRV system
5
No duct
(Air flow
setting)
With duct
(fan off)
—
—
—
—
Setting for cold
areas
(Fan operation
selection for
heater
thermostat OFF)
—
—
No duct
With duct
Fan off
Fan L
Fan off
Fan L
Centralized /
individual setting
7
Centralized
Individual
—
—
—
—
Centralized zone
interlock setting
8
No
Yes
Priority on
Operation
—
—
—
Pre-heat time
extension setting
9
0
30 min.
60 min.
90 min.
—
—
External signal
setting JC / J2
18(28)
0
Last
command
Priority on
external
input
—
—
—
—
Setting for direct
power-on
1
Off
On
—
—
—
—
Auto restart
setting
2
Off
On
—
—
—
—
External
damper
operation
Refer to P26
3
—
—
On
—
—
—
Summary of Contents for VAM 1000FAVE
Page 5: ...SiE71 202 iv Table of Contents ...
Page 13: ...General Constructions SiE71 202 4 General Constructions ...
Page 37: ...Control Functions SiE71 202 28 Control Functions ...
Page 41: ...Circuit Operations SiE71 202 32 Circuit Operations ...
Page 73: ...Supplementary Explanation SiE71 202 64 Supplementary Explanation ...
Page 74: ...SiE71 202 Appendix 65 Part 9 Appendix 1 Appendix 66 1 1 Wiring Diagram 66 ...
Page 77: ...Appendix SiE71 202 68 Appendix ...
Page 81: ...SiE71 202 iv Index ...