Si-93
Troubleshooting
Troubleshooting
43
1.13
Overlapping Central Control Address
Remote Controller
LCD Display
Error Code
UUU
UCCCC
Inspection
4
Unit No.
4
LED Indication
Remote Controller
4
Main Unit
5
Error Detection
Method
Remote controller microcomputer checks for double-setting of addresses.
Error Generating
Conditions
When same address is set to two or more units.
Possible Causes
■
Overlapping of central control address
■
Faulty remote control
Troubleshooting
Change central
control address
settings using remote
controller.
Then, turn off power,
and restart.
Does
equipment reset
properly?
YES
Replace remote controller.
End of correction procedure.
(HF012)
NO
Summary of Contents for VAM 1000EJ
Page 5: ...Si 93 iv Table of Contents ...
Page 7: ...Introduction Si 93 vi 1 1 1 Cautions in Repair Warning ...
Page 8: ...Si 93 Introduction vii ...
Page 11: ...Si 93 2 General Constructions ...
Page 15: ...Si 93 6 Operation ...
Page 21: ...Si 93 12 Maintenance ...
Page 27: ...Si 93 18 Control Functions ...
Page 35: ...Si 93 26 Circuit Operations ...
Page 39: ...Si 93 30 Troubleshooting ...
Page 59: ...Troubleshooting Si 93 50 Troubleshooting ...
Page 61: ...Si 93 52 Supplementary Explanation ...
Page 72: ...Si 93 Appendix 63 Part 8 Appendix 1 Appendix 65 1 1 Wiring Diagram 65 ...
Page 73: ...Si 93 64 Appendix ...
Page 74: ...Si 93 Appendix Appendix 65 1 Appendix 1 1 Wiring Diagram VAM500EJVE VAM800EJVE VAM1000EJVE ...
Page 75: ...Appendix Si 93 66 Appendix VAM2000EJVE ...
Page 79: ...Si 93 iv Index ...