Troubleshooting by Error Codes
SiUS281811EA
228
Part 6 Service Diagnosis
Reference
4.11 Indoor Fan Motor Status Abnormality
Error Code
A6-20
Applicable
Models
FTQ-TA
Outline
The indoor unit periodically receives control status information from the fan motor.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the information shows Power Limit or Temp Limit status, it will be deemed a MOTOR LIMIT
abnormal operation. (The system can keep operating.)
If the information shows Motor Lost Control or Current Trip status, it will be deemed a MOTOR
TRIP abnormal operation. (The system stops operating.)
Error Reset
Conditions
If the indoor unit stops receiving abnormal information, the error will be cleared.
Supposed
Causes
Fan or motor obstruction
Blocked filters
Power interruption (low voltage)
Incorrect wiring
Blockage in the airflow (ductwork) or ductwork undersized
High loading conditions
Corrective
Actions
Check for obstruction on the fan, motor, or ductwork.
Clean filters.
Check filters, grille, duct system, heat exchanger air inlet/outlet for blockages.
Verify the input voltage at the motor.
Check wiring.
Replace motor.
CHECK 19
Refer to page 311.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...