3.4 Error Codes and Corresponding Measures
Please check the remote controller connected to the indoor unit for verification.
Error code
Description
Solution
Primary
code
Sub
code
E3
01
High pressure switch activated (S1PH)
Check the stop valve or (field) piping
abnormality or the airflow on the air
cooling heat exchanger.
02
• Too much refrigerant charged
• Stop valve closed
• Check the amount of refrigerant and
recharge the unit.
• Open the stop valve.
13
Stop valve closed (liquid).
Open the liquid stop valve.
18
• Too much refrigerant charged
• Stop valve closed
• Check the amount of refrigerant and
recharge the unit.
• Open the stop valve.
E4
01
Defective low pressure:
• Stop valve closed
• Refrigerant undercharged
• Defective indoor unit
• Open the stop valve.
• Check the amount of refrigerant and
recharge the unit.
• Check the user interface display.
• Check the transmission wiring
between the indoor and outdoor units.
E9
01
Defective electronic expansion valve
(Subcooling) (30/36/42/48 class: Y3E)
Check the connection of the PCB or
the actuator.
04
Defective electronic expansion valve (Main)
(Y1E)
Check the connection of the PCB or
the actuator.
F3
01
Discharge pipe temperature too high:
• Stop valve closed
• Refrigerant undercharged
• Open the stop valve.
• Check the amount of refrigerant and
recharge the unit.
F6
02
• Too much refrigerant charged
• Stop valve closed
• Open the stop valve.
• Check the amount of refrigerant and
recharge the unit.
H9
01
Defective outdoor air thermistor (R1T)
Check the connection of the PCB or
the actuator.
J3
16
Defective discharge pipe thermistor (R2T):
Tripping
Check the connection of the PCB or
the actuator.
17
Defective discharge pipe thermistor (R2T):
Short circuit
Check the connection of the PCB or
the actuator.
J5
01
Defective suction pipe thermistor (R3T and
R5T): Tripping
Check the connection of the PCB or
the actuator.
J6
01
Defective outdoor heat exchanger deicer
thermistor (R4T)
Check the connection of the PCB or
the actuator.
J7
01
Defective heat exchanger liquid pipe
thermistor (R7T)
Check the connection of the PCB or
the actuator.
J9
01
Defective subcooling heat exchanger gas pipe
thermistor (R6T: 30/36/42/48 class only)
Check the connection of the PCB or
the actuator.
JA
06
Defective high pressure sensor (S1NPH):
Tripping
Check the connection of the PCB or
the actuator.
07
Defective high pressure sensor (S1NPH):
Short circuit
Check the connection of the PCB or
the actuator.
JC
06
Defective low pressure sensor (S1NPL):
Tripping
Check the connection of the PCB or
the actuator.
07
Defective low pressure sensor (S1NPL): Short
circuit
Check the connection of the PCB or
the actuator.
P1
01
Inverter unbalanced power supply voltage
Check if the power supply meets the
specifications.
U2
01
Inverter insufficient voltage
Check if the power supply meets the
specifications.
02
Inverter power supply phase missing
Check if the power supply meets the
specifications.
U3
03
System test operation not yet executed (Test
operation cannot be executed.)
Execute system test operation.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...