Part 5 Field Settings and Test Operation
1.6 Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller
ON/OFF can be limited in accordance with the combination conditions. (Refer to information in the
next page.)
Centralized controller is normally available for operations. (Except when centralized monitor is
connected)
Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by centralized remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by centralized remote controller only, and OFF by remote
controller only.
Centralized
Used when you want to turn ON by centralized remote controller only, and turn ON/OFF
freely by remote controller during set time.
Individual
Used when you want to turn ON/OFF by both centralized remote controller and remote
controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by centralized remote controller when time of system start is programmed.
Summary of Contents for SkyAir RZR-TA Series
Page 1: ...Service Manual Cooling Only 60 Hz Heat Pump 60 Hz RZR TA RZQ TA Series SiUS281811EA...
Page 202: ...SiUS281811EA 196 Part 6 Service Diagnosis 5 15 Fan Motor Connector Check for FTQ TA 311...
Page 323: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 317 RZR18 24TAVJUA RZQ18 24TAVJUA 3D124495...
Page 327: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 321 FHQ18 24 30PVJU FHQ36 42MVJU 3D048116C...
Page 328: ...Wiring Diagrams SiUS281811EA 322 Part 7 Appendix FAQ18 24TAVJU 3D114844B...
Page 329: ...SiUS281811EA Wiring Diagrams Part 7 Appendix 323 FBQ18 24 30 36 42 48PVJU 3D065984J...