SiUS281811EA
Other Control
Part 4 Functions and Control
123
5. Other Control
5.1 Demand
Operation
In order to reduce power consumption, the outdoor unit capacity is reduced forcibly with control by
using Demand Setting 1.
To enable this operation, the additional setting of Constant Demand Setting is required.
∗
Other protection control functions have precedence over the above operation.
5.2 Heating
Operation
Prohibition
Heating operation is prohibited above 24°CDB (75.2°FDB) outdoor air temperature.
Demand setting 1
Level
Standard for upper limit of power consumption
Level 1
Approx. 60%
Level 2 (Factory setting)
Approx. 70%
Level 3
Approx. 80%