Troubleshooting by Error Code
SiME281906E
145
Part 6 Service Diagnosis
Reference
Reference
5.16 Low Pressure Abnormality
Applicable
Models
All outdoor unit models
Error Code
E4
Method of Error
Detection
Cooling:
Detect errors by the indoor heat exchanger middle thermistor (R3T).
Error Decision
Conditions
When the detection pressure is the following value;
0.12 MPa or less continues for 5 minutes
(Ref.: Equivalent saturation temperature –35°C)
Supposed
Causes
Stop valve is not opened.
Disconnection of indoor heat exchanger middle thermistor
Defective thermistors
Defective outdoor unit main PCB
Abnormal drop of low pressure
Troubleshooting
CHECK 1
Refer to page 192.
CHECK 3
Refer to page 195.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Open the stop valve.
Is the stop valve open?
NO
Connect the connector
properly.
NO
Replace the indoor heat
exchanger middle thermistor.
NO
Replace the outdoor unit main
PCB (A1P).
Is low pressure
abnormally low?
Is it normal?
Correct the refrigerant system
defect.
NO
YES
YES
YES
CHECK 3
Remove the thermistor from the
indoor unit PCB and measure
resistance.
YES
CHECK 1
Is the
indoor heat exchanger
middle thermistor properly
connected to the indoor unit
PCB?