SiME281906E
Troubleshooting by Error Code
Part 6 Service Diagnosis
140
Note(s)
5.12 Combination Error between Indoor Unit PCB and Fan
PCB
Applicable
Models
All indoor unit models
Error Code
C6
Method of Error
Detection
Conduct open line detection with fan PCB using indoor unit PCB (A1P).
Error Decision
Conditions
The communication data of fan PCB is determined as incorrect
Supposed
Causes
Defective fan PCB
Wrong capacity setting adaptor.
Defective field setting
Troubleshooting
1. Refer to
Defective Capacity Setting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace it with correct fan
PCB (A2P).
Does the
fan PCB (A2P) part No.
match that of the spare parts
list?
Attach the correct capacity
setting adaptor. (
∗
1)
Was the
correct capacity
setting adaptor attached when
installing a spare PCB?
NO
Was indoor unit
control PCB (A1P) replaced with
a spare PCB?
NO
After establishing
transmission for indoor and
outdoor, diagnose the
operation again.
After establishing
transmission for indoor and
outdoor, diagnose the
operation again.
NO
YES
YES
YES