Symptom-Based Troubleshooting
SiME281906E
103
Part 6 Service Diagnosis
2.2 Safety Devices
2.2.1 Indoor Unit
2.2.2 Outdoor Unit
Model
Fuse
FDMF-A
A1P
F1U (3.15 A, 250 V)
A2P
F2U (5.0 A, 250 V)
F4U (6.3 A, 250 V)
Model
Fuse
High pressure switch
RZF18/24AVMK
A1P
F1U (6.3 A, 250 V)
F2U (30 A, 250 V)
F6U (3.15 A, 250 V)
S1PH
Open: 4.15
(MPa)
Close: 3.2 ± 0.15 (MPa)
RZF30/36AVMK
A1P
F1U (31.5 A, 250 V)
F2U, F3U (6.3 A, 250 V)
F6U (5 A, 250 V)
+ 0
– 0.15