SiME281906E
Symptom-Based Troubleshooting
Part 6 Service Diagnosis
102
2. Symptom-Based Troubleshooting
2.1 All Indoor Units
Symptom
Details of Measures
1
Equipment does not operate.
Refer to page 104.
2
Indoor fan operates, but compressor does not operate.
Refer to page 106.
3
Cooling operation starts but stops immediately.
Refer to page 107.
4
After unit shuts down, it cannot be restarted for a while.
Refer to page 108.
5
Equipment operates but does not provide cooling.
Refer to page 110.
6
Equipment discharges white mist.
Refer to page 112.
7
Equipment produces loud noise or vibration.
Refer to page 113.
8
Equipment discharges dust.
Refer to page 115.
9
Defrost lamp on the receiver for wireless remote
controller is blinking.
Refer to page 116.
10
Equipment emits odor.
Odors and cigarette smoke from the room accumulate
inside the indoor unit and are discharged with air. Clean
the inside of the indoor unit.
11
Indoor fan operates in L tap for 1 minute in program dry
mode even if compressor is not operating.
Normal.
The monitoring function forcibly operates the fan for 1
minute.
12
Drain pump operates when equipment is not operating.
Normal.
The drain pump continues to operate for several minutes
after equipment is turned OFF.
13
Remote controller thermistor cannot be used with a
group controller.
Normal.
Remote controller thermistor cannot be used in group
control.
14
When operating in remote controller thermistor, the
thermostat turns OFF before temperature of remote
control reaches the set temperature.
Normal.
Control may be conducted with the suction air
temperature (body thermostat), concurrently with the set
temperature.
15
When an error occurs on the unit with an individual
remote controller during group control with one remote
controller, the address display on the individual remote
controller shows
0
regardless of the address setting.
Normal.
Address display of an individual remote controller is
always
0
.
16
The remote controller display goes blank during
operation.
This is not a failure.
BRC1E63 is designed to turn the display off after a
certain amount of time without activity, in order to save
power.