3
2
• Split - Sky Air • RZAG-MV1
3
• Outdoor Unit • RZAG-MV1
2
Specifications
2-1 Capacity and Power input
FCAHG100G/
RZAG71MV1
FCAHG71G/
RZAG71MV1
FCAHG140G/
RZAG100MV1
FCAHG100G/
RZAG100MV1
FCAHG125G/
RZAG125MV1
FCAHG140G/
RZAG140MV1
Indoor unit
FCAHG100GV
EB
FCAHG71GV
EB
FCAHG140GV
EB
FCAHG100GV
EB
FCAHG125GV
EB
FCAHG140GV
EB
Outdoor unit
RZAG71M7V1B
RZAG100M7V1B
RZAG125M7V
1B
RZAG140M7V
1B
Cooling capacity
Nom.
kW
6.80 (1)
9.50 (1)
12.1 (1)
13.4 (1)
Heating capacity
Nom.
kW
7.50 (2)
10.8 (2)
13.5 (2)
15.5 (2)
Space cooling
Energy efficiency class
A++
-
Capacity
Pdesign
kW
6.80
9.50
12.1
13.4
SEER
7.05
7.72
7.93
7.35
8.02
7.93
η
s,c
%
-
318
314
Annual energy consumption
kWh/a
338
308
419
452
905
1,014
A Condition (35°C -
27/19)
Pdc
kW
6.80
9.50
12.10
13.40
EERd
4.41
4.39
4.80
5.06
4.30
3.89
Power input
kW
1.54
1.55
1.98
1.88
2.81
3.44
B Condition (30°C -
27/19)
Pdc
kW
5.02
7.00
8.92
9.88
EERd
6.20
6.12
6.45
5.80
6.36
6.20
Power input
kW
0.81
0.82
1.09
1.21
1.40
1.59
C Condition (25°C -
27/19)
Pdc
kW
3.23
4.50
4.52
5.74
6.35
EERd
8.70
10.10
10.21
9.22
9.36
9.38
Power input
kW
0.37
0.32
0.44
0.49
0.61
0.68
D Condition (20°C -
27/19)
Pdc
kW
3.16
4.13
4.32
4.26
4.31
EERd
11.02
13.62
11.91
11.03
12.48
12.63
Power input
kW
0.29
0.23
0.35
0.39
0.34
Space heating
(Average climate)
Energy efficiency class
A+
A++
-
Capacity
Pdesign
kW
4.70
9.52
SCOP/A
4.20
4.61
4.70
4.81
4.53
4.44
SCOPnet/A
4.20
4.61
4.70
4.81
4.53
4.44
η
s,h
%
-
178
175
Annual energy consumption
kWh/a
1,567
1,427
2,836
2,771
2,942
3,002
Required back up heating cap at design
conditions
kW
0.00
TOL
Tol (temperature
operating limit)
°C
-10
Pdh (declared
heating cap)
kW
4.70
9.52
COPd (declared COP)
2.62
2.59
2.25
2.24
2.02
2.07
Power input
kW
1.80
1.82
4.23
4.25
4.72
4.60
TBivalent
Tbiv (bivalent
temperature)
°C
-10
Pdh (declared
heating cap)
kW
4.70
9.52
COPd (declared COP)
2.62
2.59
2.25
2.24
2.02
2.07
Power input
kW
1.80
1.82
4.23
4.25
4.72
4.60
A Condition (-7°C)
Pdh (declared
heating cap)
kW
4.16
8.42
COPd (declared COP)
2.96
2.97
2.72
2.73
2.49
2.51
Power input
kW
1.40
3.09
3.08
3.39
3.35
B Condition (2°C)
Pdh (declared
heating cap)
kW
2.53
5.13
COPd (declared COP)
4.28
4.67
4.99
5.03
4.85
4.76
Power input
kW
0.59
0.54
1.03
1.02
1.06
1.08
C Condition (7°C)
Pdh (declared
heating cap)
kW
2.19
2.08
3.30
3.55
3.30
COPd (declared COP)
5.12
5.91
5.71
5.85
5.68
5.39
Power input
kW
0.43
0.35
0.58
0.56
0.63
0.61
D Condition (12°C)
Pdh (declared
heating cap)
kW
2.63
2.51
3.45
1.46
4.16
3.42
COPd (declared COP)
6.63
7.72
7.18
7.35
7.03
6.77
Power input
kW
0.40
0.33
0.48
0.20
0.59
0.50
Pto (Thermostat off)
W
12 / 0
-