3
3
• Split - Sky Air • RZAG-MV1
19
• Outdoor Unit • RZAG-MV1
3
Electrical data
3 - 1
Electrical Data
AZAS-MV1
AZAS-MY1
RZAG-MV1
RZAG-MY1
RZASG-MV1
RZASG-MY1
Symbols
MCA: Minimum Circuit Ampere [A]
TOCA: Total overcurrent amps [A]
MFA: Maximum Fuse Ampere [A]
MSC: Maximum current of the starting compressor [A]
RLA: Rated load amps [A]
OFM: Outdoor fan motor
IFM: Indoor fan motor
FLA: Full Load Ampere [A]
KW: Fan motor rated output [kW]
Notes
1. The RLA is based on the following conditions.
Cooling
Indoor temperature 27.0°C DB / 19.0°C WB
Outdoor temperature 35.0°C DB
Heating
Indoor temperature 20.0°C DB
Outdoor temperature 7.0°C DB / 6.0°C WB
2. TOCA is the total value of each overcurrent set.
3. Voltage range
The units are suitable for use with electrical systems in which the voltage supplied to the unit terminals is not below or above the listed range limits.
4. The maximum allowable voltage that is unbalanced between phases is 2%.
5. MCA is the maximum input current.
The capacity of the MFA must be greater than that of the MCA.
Select the MFA according to the table.
6. Select the wire size according to the MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interruptor.
Earth leakage circuit breaker
3D110014A
RZAG71-100MV1
FCAHG71GVEB
RZAG71M7V1B
17,5
㸫
20
㸫
15,5
0,094
0,8
0,091
0,5
FCAG35AVEB
x2
RZAG71M7V1B
17,6
㸫
20
㸫
15,5
0,094
0,8
0.044 x2
0.3 x2
FCAG71AVEB
RZAG71M7V1B
17,4
㸫
20
㸫
15,5
0,094
0,8
0,054
0,4
FFA35A2VEB
x2
RZAG71M7V1B
17,8
㸫
20
㸫
15,5
0,094
0,8
0.050 x2
0.4 x2
FBA35A2VEB
x2
RZAG71M7V1B
18,2
㸫
20
㸫
15,5
0,094
0,8
0.089 x2
0.6 x2
FBA71A2VEB
RZAG71M7V1B
17,6
㸫
20
㸫
15,6
0,094
0,8
0,070
0,5
FNA35A2VEB
x2
RZAG71M7V1B
17,3
㸫
20
㸫
15,5
0,094
0,8
0.034 x2
0,3
FUA71AVEB
RZAG71M7V1B
17,9
㸫
20
㸫
15,5
0,094
0,8
0,046
0,9
FAA71AUVEB
RZAG71M7V1B
17,4
㸫
20
㸫
15,5
0,094
0,8
0,048
0,4
FVA71AMVEB
RZAG71M7V1B
17,6
㸫
20
㸫
15,5
0,094
0,8
0,117
0,6
FDXM35F3V1B
x2
RZAG71M7V1B
17,6
㸫
20
㸫
15,5
0,094
0,8
0.034 x2
0.3 x2
FHA35AVEB
x2
RZAG71M7V1B
18,2
㸫
20
㸫
15,5
0,094
0,8
0.060 x2
0.6 x2
FHA71AVEB
RZAG71M7V1B
17,8
㸫
20
㸫
15,5
0,094
0,8
0,091
0,8
FCAHG100GVEB
RZAG100M7V1B
27,4
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,221
1,3
FCAG35AVEB
x3
RZAG100M7V1B
26,9
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.044 x3
0.3 x3
FCAG50AVEB
x2
RZAG100M7V1B
26,6
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.039 x2
0.3 x2
FCAG100AVEB
RZAG100M7V1B
26,7
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,117
0,7
FFA35A2VEB
x3
RZAG100M7V1B
27,2
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.050 x3
0.4 x3
FFA50A2VEB
x2
RZAG100M7V1B
26,8
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.050 x2
0.4 x2
FBA35A2VEB
x3
RZAG100M7V1B
27,9
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.089 x3
0.6 x3
FBA50A2VEB
x2
RZAG100M7V1B
27,2
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.089 x2
0.6 x2
FBA100A2VEB
RZAG100M7V1B
27,0
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,127
1,0
FNA35A2VEB
x3
RZAG100M7V1B
26,9
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.034 x3
0.3 x3
FNA50A2VEB
x2
RZAG100M7V1B
27,0
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.060 x2
0.5 x2
FUA100AVEB
RZAG100M7V1B
27,4
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,106
1,3
FAA100AUVEB
RZAG100M7V1B
26,4
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,064
0,4
FVA100AMVEB
RZAG100M7V1B
27,2
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,238
1,2
FDXM35F3V1B
x3
RZAG100M7V1B
26,9
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.034 x3
0.3 x3
FDXM50F3V1B
x2
RZAG100M7V1B
27,0
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.060 x2
0.5 x2
FHA35AVEB
x3
RZAG100M7V1B
27,9
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.060 x3
0.6 x3
FHA50AVEB
x2
RZAG100M7V1B
27,2
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0.060 x2
0.6 x2
FHA100AVEB
RZAG100M7V1B
27,4
㸫
32
㸫
23,5
0.094+0.094
0.75+0.75
0,150
1,3
FLA
Compressor
OFM
IFM
Indoor
Outdoor
Power supply
Voltage
range
MCA
TOCA
MFA
MSC
RLA
kW
FLA
kW
50Hz ~
220-240V
Minimum: 198 V
Ma
x
imum 264 V
50Hz ~
220-240V
Minimum: 198 V
Ma
x
imum 264 V
3D110014A