6
|
Technical data
Service manual
179
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
6.8.2 Field settings: Indoor unit
To retrieve the field settings
Via the wired remote controller BRC1E
INFORMATION
Images are in English and for reference ONLY. For more details on the BRC1E please
refer to the user manual.
To access the field settings screen
#
Action
Result
1
Go to the basic screen.
Cool
Set to
28
°C
2
Press at least 4 seconds while the
backlight of the screen is lit.
The Service Settings menu is
displayed.
3
Select Field Settings.
Return
Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
4
Press.
The Field Settings screen is
displayed.
In case of individual setting per indoor unit
#
Action
Result
1
Highlight the Mode.
Select the desired Mode No.
The desired field setting mode is
selected.
2
When Mode No. such as 20, 21,
22, 23, 25 are selected, highlight
the Unit No..
Select the Indoor unit No. to be
set.
▪
The indoor unit for which you
want to set the field settings is
selected.
▪
Current settings are displayed.
▪
Second Code No. "-" means no
function.
Field Settings
Unit No.
0
Mode
20
Setting
Return