6
|
Technical data
Service manual
170
250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
6.8 Field settings
6.8.1 Field settings: Outdoor unit
To access mode 1 or 2
1
Check if the unit is in normal mode. If NOT in normal mode, push BS1 to
return to normal mode. 7‑segment display indication state will be as shown:
Result:
2
7‑segment display indications:
Off
Blinking
On
3
BS1 is used to change the mode you want to access.
Access
Action
Mode 1
Push BS1 one time.
7‑segment display indication changes to:
Mode 2
Push BS1 for at least 5 seconds.
7‑segment display indication changes to:
To use mode 1
Mode 1 is used to monitor the status of the unit.
What
How
Changing and accessing the
setting in mode 1
Once mode 1 is selected (push BS1 one time),
you can select the wanted setting. It is done by
pushing BS2.
Accessing the selected setting's value is done by
pushing BS3 one time.
To quit and return to the initial
status
Press BS1.
Example:
Checking the content of parameter [1‑20] (to know the outdoor unit air sensor
temperature).
[A‑B]=C in this case defined as: A=1; B=20; C=the value we want to know/monitor:
1
Make sure the 7‑segment display indication is as during normal operation
(default situation when shipped from factory). 7‑segment display indications:
Off
Blinking
On
2
Push BS1 one time.
Result:
Mode 1 is accessed:
3
Push BS2 20 times.
Result:
Mode 1 setting 20 is addressed:
Summary of Contents for Sky Air Advance RZA200D7Y1B
Page 1: ...Service manual Sky Air Advance series RZA200D7Y1B RZA250D7Y1B ...
Page 190: ......
Page 191: ......
Page 192: ...ESIE19 13A 2020 05 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...