12 Technical data
Installer and user reference guide
57
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1A – 2018.01
12.9
Field settings on the user interface – overview
1st code 2nd
code
Setting name
Date
Value
Date
Value
Default
value
Range
Step
Unit
0
User interface setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
02
Not applicable. Do not change the default value.
1
—
—
—
—
—
03
Status: space heating schedule timer mode (Method 1=1 / Method
2=0)
1 (ON)
0/1
—
—
—
04
Status: space cooling schedule timer mode (Method 1=1 / Method
2=0)
1 (ON)
0/1
—
—
—
1
Settings are not applicable
00
Not applicable. Do not change the default value.
1
—
—
—
—
—
01
Not applicable. Do not change the default value.
1:00
—
—
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
—
—
03
Not applicable. Do not change the default value.
15:00
—
—
—
—
—
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
—
01
Setback operation start time
23:00
0:00~23:00
1:00
hour
—
02
Setback operation stop time
5:00
0:00~23:00
1:00
hour
—
3
Weather dependent setpoint
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
—
01
High ambient temperature (Hi_A)
15
10~20
1
°C
—
02
Setpoint at low ambient temperature (Lo_Ti)
40
25~80
1
°C
—
03
Setpoint at high ambient temperature (Hi_Ti)
25
–20~5
1
°C
—
4
Settings are not applicable
00
Not applicable. Do not change the default value.
1
—
—
—
—
—
01
Not applicable. Do not change the default value.
Fri
—
—
—
—
—
02
Not applicable. Do not change the default value.
23:00
—
—
—
—
—
5
Automatic setback and disinfection setpoint
00
Not applicable. Do not change the default value.
70
—
—
—
—
—
01
Not applicable. Do not change the default value.
10
—
—
—
—
—
02
Leaving water setback temperature
5
0~10
1
°C
—
03
Room setback temperature
18
17~23
1
°C
—
04
Not applicable. Do not change the default value.
1
—
—
—
—
—
6
Option setup
01
Optional room thermostat installed
0
0~2
—
—
7
Option setup
00
Forced pump operation
1 (ON)
0/1
—
—
8
Option setup
00
User interface temperature control
0 (OFF)
0/1
—
—
01
Not applicable. Do not change the default value.
1
—
—
—
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
—
—
04
Status: freeze-up prevention
0
0~2
1
—
9
Automatic temperature compensation
00
Leaving water temperature compensation value (heating)
0
–2~2
0.2
°C
—
01
Leaving water thermistor auto corrective function
1 (ON)
0/1
1
—
02
Not applicable. Do not change the default value.
0
—
—
—
—
—
03
Leaving water temperature compensation value (cooling)
0
–2~2
0.2
°C
—
04
Not applicable. Do not change the default value.
0
—
—
—
—
—
A
Option setup
00
Not applicable. Do not change the default value.
0
—
—
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
—
—
02
Allowable undershoot value for return water
5
0~15
1
°C
—
03
Allowable overshoot value for leaving water
3
1~5
0.5
°C
b
Settings are not applicable
00
Not applicable. Do not change the default value.
35
—
—
—
—
—
01
Not applicable. Do not change the default value.
45
—
—
—
—
—
02
Not applicable. Do not change the default value.
1
—
—
—
—
—
03
Not applicable. Do not change the default value.
70
—
—
—
—
—
04
Not applicable. Do not change the default value.
70
—
—
—
—
—
C
Leaving water temperature limits
00
Setpoint: heating leaving water maximum temperature
50
37~50
1
°C
—
01
Setpoint: heating leaving water minimum temperature
25
25~37
1
°C
—
02
Setpoint: cooling leaving water maximum temperature
20
18~22
1
°C
—
03
Setpoint: cooling leaving water minimum temperature
5
Q
(a)
~18
1
°C
—
04
Not applicable. Do not change the default value.
0
—
—
—
—
—