6 Installation
Installer and user reference guide
30
SERHQ020~0 SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508020-1A – 2018.01
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1
Making sure the power supply system complies with the
electrical specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor unit.
4
Connecting the main power supply.
6.9.2
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
All field wiring and components MUST be installed by a
licensed electrician and MUST comply with the applicable
legislation.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Do NOT operate the unit until the refrigerant piping is
complete. Running the unit before the piping is ready will
break the compressor.
NOTICE
If the power supply has a missing or wrong N-phase,
equipment will break down.
NOTICE
Do NOT install a phase advancing capacitor, because this
unit is equipped with an inverter. A phase advancing
capacitor will reduce performance and may cause
accidents.
NOTICE
NEVER remove a thermistor, sensor, etc., when
connecting power wiring and transmission wiring. (If
operated without thermistor, sensor, etc., the compressor
may break down.)
NOTICE
▪ The reversed phase protection detector of this product
only
functions
when
the
product
starts
up.
Consequently reversed phase detection is not
performed during normal operation of the product.
▪ The reversed phase protection detector is designed to
stop the product in the event of an abnormality when
the product is started up.
▪ Replace 2 of the 3 phases (L1, L2, and L3) during
reverse-phase protection abnormality.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
NOTICE
▪ When using the option adapter, refer to the installation
manual of the adapter.
▪ For connection wiring to indoor-outdoor transmission
F1-F2, pushbuttons BS1~BS5 and DIP switches
DS1~DS2, refer to
"6.9.7 To connect the power supply
and transmission cables" on page 33
WARNING
Do not operate the unit by short-circuiting protection device
S1PH.
NOTICE
For wiring to the central remote controller, refer to the
installation manual of the central remote controller.
NOTICE
Use insulated wire for the power cord.
NOTICE
▪ Be sure to install an earth leakage breaker that is
capable of handling high-frequency electrical noise
generated by the inverter in order to prevent
malfunctioning of the earth leakage breaker.
▪ The noise generated by the inverter must be reduced in
order to avoid interfering with other devices.
▪ The outer casing of the product may take on an
electrical charge due to leaked electrical current, which
will have to be discharged with the grounding.