background image

INSTALLATION MANUAL

 

RZQS71B7V3B
RZQS100B7V3B
RZQS125B7V3B

 

Split System air conditioners

Summary of Contents for RZQS71B7V3B

Page 1: ...INSTALLATION MANUAL RZQS71B7V3B RZQS100B7V3B RZQS125B7V3B Split System air conditioners...

Page 2: ...7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B...

Page 3: ...condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vas...

Page 4: ...ation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire...

Page 5: ...ording to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explo...

Page 6: ...oration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit...

Page 7: ...ipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...pe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impo...

Page 9: ...anch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed in four directions Figure...

Page 10: ...er to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service p...

Page 11: ...of oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preve...

Page 12: ...30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Total additional charge amount R R1 R2 kg Table 2 Length unit m additional charging of refrigerant unit kg Example 1 1 G1 L1 35 m G2 L2 L3 7...

Page 13: ...ze bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure b...

Page 14: ...wiring works Form the wires and fix the cover firmly so that the cover may be fit in properly Precautions on wiring of power supply and inter unit wiring Use a round crimp style terminal for connecti...

Page 15: ...ept displaying the heating symbol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unus...

Page 16: ...or code U4 or UF is displayed on the remote controller check the inter unit branch wiring connection The reversed phase protection detector of this product only works during the initialisation stage a...

Page 17: ...or air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high S1PL Pre...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW32097 1A...

Reviews: