ESIE15-13C
Field Setting from Remote Controller
Field Setting
77
2.7
Setting for Low Humidity Application
Purpose
Can be set when using the RZQG units for year round cooling in low humidity applications such
as computer rooms (EDP rooms), technical rooms, etc...to increase the capacity of the unit.
Definition of Low
Humidity Area
Caution
When using the "LH settings" outside the "Low Humidity Area" there is an increased risk of ice
accumulation on the indoor coil or water blowing out from the indoor unit.
Function details
Parameters
Relative
Humidity
(%)
Setting is only allowed in this area
Indoor side temperature DB (˚C)
Factory setting
Low humidity application
setting
Low humidity appli
freeze up operation
prevention
Field Setting
16(26)-2-01
16(26)-2-03
16(26)-2-04
Compressor control
The compressor frequency is controlled in function of the target evaporating temperature.
The target evaporating temperature is controlled in function of the cooling load.
Minimum target Te = 2°C
Minimum target Te = 0°C
Initial minimum target Te =
2°C, but can be changed in
function of actual Te, to avoid
freeze up activation:
Te
≤
-1°C for 20 minutes
accumulated => Change
target Te
≥
5°C
Te
≤
-1°C for 30 minutes
accumulated => Change
target Te
≥
8°C
See graph 1
See graph 2
See graph 3
Freeze protection
function
Start
Te
≤
-1°C for 40 minutes
accumulated
OR
Te
≤
A°C for 1 minute
continuous
(Indoor decision)
Te
≤
-1°C for 40 minutes
accumulated
OR
Te
≤
-3°C for 1 minute
continuous
(Outdoor decision)
Te
≤
-1°C for 40 minutes
accumulated
OR
Te
≤
A°C for 1 minute
continuous
(Outdoor decision)
End
Te > 7°C for 10 minutes
continuously.
(Indoor decision)
Te > 7°C for 3 minutes
continuously
OR
Te > 4°C for 20 minutes
continuously
(Outdoor decision)
Te > 7°C for 3 minutes
continuously
OR
Te > 4°C for 20 minutes
continuously
(Outdoor decision)
FCQG
FHQG
A
-5°C
-3°C
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...