Troubleshooting by Remote Controller
ESIE15-13C
190
Service Diagnosis
Check for Power Transistor
Judgement according to the continuity check by using an analog tester:
(1) Do not touch the charged area (high voltage) for 10 minutes after turning the power supply off.
(2) If you must touch such an area, make sure that the power supply voltage of power transistor is 50 V or
less.
(3) Disconnect the connector of the outdoor unit fan motor.
When the outdoor unit fan is rotating against a strong wind, the condenser is charged and electric shock
may result. Therefore, disconnect the connector from the outdoor unit fan motor after confirming that the
outdoor unit fan has stopped.
(4) Before measuring the continuity, disconnect the connection between compressor and power transistor.
(5) Measure the continuity in the following procedure.
[Judgement] Normal if the continuity check results in the following.
Power transistor (on inverter PCB)
Note:
* If there is continuity, the resistance should be the same as each phase.
* If a digital tester is used for the measurement of continuity,
∞
and continuity may be reversed.
CHECK 4
∗
∗
C+— U
Continuity
C+
— V
Continuity
C+
— W
Continuity
U —
C+
∞
V —
C+
∞
W —
C+
∞
C- — U
∞
C- — V
∞
C- — W
∞
U —
C-
Continuity
V — C-
Continuity
W — C-
Continuity
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...