ESIE15-13C
Troubleshooting by Remote Controller
Service Diagnosis
123
4.3
Safety Devices
4.3.1 Outdoor Unit
4.3.2 Indoor Unit
Model
High pressure switch
Fuse
Open
Close
RZQG71L
4.0 MPa +0/– 0.15
3.0 MPa ± 0.15
6.3A/250V (F1U), 3.15A/250V (F6U)
RZQG100L
6.3A/250V (F1U, F2U, F3U),
5A/250V (F6U)
RZQG125L
RZQG140L
Model
Thermal protector
Fuse
Abnormal
Reset (automatic)
FCQG
—
—
N.A.
FHQG
3.15A/250V (F1U)
Summary of Contents for RZQG71L9V1