Si281314E
Procedure to Remove Compressor
Removal Procedure
11
10.Procedure to Remove Compressor
Procedure
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
Collect the refrigerant.
Remove the outside
panels, their parts, and
the switch box, following
the procedure indicated at
"Removing Outside
Panels and Related Parts"
and other instructions.
Be sure to confirm that the
refrigerant is completely
collected before starting the
work.
The color of each terminal
One of the fixing nuts of the
compressor is located at the
outer side of the partition
plate.
1
Remove the fixing plate
for the stop valve after
removing the 5 screws.
2
Remove the sound
insulation (1).
3
Remove the terminal
cover, after pushing the
projective parts from
the both sides.
4
Remove the lead wire
from the terminal (2).
5
Pull out the sound
insulation by unwinding
the strings (2 locations).
6
Remove the nuts that
fix the compressor. (All
the equipments are
fixed with 3 nuts).
7
Cut off the brazing (2
locations).
8
Pull out the compressor
by lifting upward.
Fixing nuts
Fixing plate for the stop valve
Brazing
Sound insulation (1)
Sound insulation (2)
String
Terminal cover
V
U
W
U: Red V: White W: Blue
Rubber bush
Glass terminal