8 Hand-over to the user

Installer reference guide

25

RZASG71~Y1
Sky Air Advance-series
4P486047-1 – 2017.04

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  unit  PCB  has

blown out.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

NOTICE

▪ The reversed phase protection detector of this product

only 

functions 

when 

the 

product 

starts 

up.

Consequently  reversed  phase  detection  is  not
performed during normal operation of the product.

▪ The  reversed  phase  protection  detector  is  designed  to

stop  the  product  in  the  event  of  an  abnormality  when
the product is started up.

▪ Replace  2  of  the  3  phases  (L1,  L2,  and  L3)  during

reverse-phase protection abnormality.

8

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do in relation to maintaining the unit.

9

Maintenance and service

NOTICE

Maintenance  must  be  done  by  an  authorised  installer  or
service agent.

We  recommend  to  do  maintenance  at  least  once  a  year.
However,  applicable  legislation  might  require  shorter
maintenance intervals.

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

9.1

Overview: Maintenance and
service

This chapter contains information about:

▪ The yearly maintenance of the outdoor unit

9.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

9.2.1

To prevent electrical hazards

When performing service to inverter equipment:

1

Do not open the electrical component box cover for 10 minutes
after the power supply is turned off.

2

Measure  the  voltage  between  terminals  on  the  terminal  block
for power supply with a tester and confirm that the power supply
is  shut  off.  In  addition,  measure  points  as  shown  in  the  figure
below, with a tester and confirm that the voltage of the capacitor
in the main circuit is less than 50 V DC.

       

A1P

C–

C+

C–

C+

V1

Y1

    

3

To  prevent  damaging  the  PCB,  touch  a  non-coated  metal  part
to  eliminate  static  electricity  before  pulling  out  or  plugging  in
connectors.

4

Pull  out  junction  connectors  for  the  fan  motors  in  the  outdoor
unit before starting service operation on the inverter equipment.
Be  careful  not  to  touch  the  live  parts.  (If  a  fan  rotates  due  to
strong  wind,  it  may  store  electricity  in  the  capacitor  or  in  the
main circuit and cause electric shock.)

Junction connectors

X106A for M1F

X107A for M2F

5

After the service is finished, plug the junction connector back in.
Otherwise  the  malfunction  code  E7  will  be  displayed  and
normal operation will not be performed.

For  details  refer  to  the  wiring  diagram  labelled  on  the  back  of  the
service cover.

Summary of Contents for RZASG100M7V1B

Page 1: ...nstaller reference guide Sky Air Advance series English Installer reference guide Sky Air Advance series RZASG71M2V1B RZASG100M7V1B RZASG125M7V1B RZASG140M7V1B RZASG100M7Y1B RZASG125M7Y1B RZASG140M7Y1...

Page 2: ...recautions when checking the refrigerant piping 16 6 5 3 Checking refrigerant piping Setup 16 6 5 4 To check for leaks 16 6 5 5 To perform vacuum drying 17 6 6 Charging refrigerant 17 6 6 1 About char...

Page 3: ...OT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it...

Page 4: ...ake sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It state...

Page 5: ...earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when layi...

Page 6: ...do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenance and service Ho...

Page 7: ...n manual of the refrigerant branch kit Demand adaptor kit SB KRP58M52 Includes the additional mounting plate EKMKSA2 Can be used for the following Low noise To lower the operation sound of the outdoor...

Page 8: ...ght be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level is less than 70 dBA In pl...

Page 9: ...rresponds with the actual highest unit L1 Main piping L2 L7 Branch piping H1 Height difference between the highest indoor unit and the outdoor unit H2 Height difference between the highest and the low...

Page 10: ...win L2 L3 Limit L4 L5 Limit L6 L7 Limit L2 L4 L3 L7 Limit 10 m 6 Maximum height between indoor and outdoor Pair twin triple and double twin H1 Limit 30 m 7 Maximum height between indoors Pair N A Twin...

Page 11: ...ing Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFORMATION For installation of the indoor unit mounting the indoor unit...

Page 12: ...e unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping see the following illustration INFORMATION If necessary you can use a drain plug kit field supply to...

Page 13: ...thing but the designated refrigerant to get mixed into the refrigerant cycle e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used f...

Page 14: ...d film on the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough...

Page 15: ...oor unit Piping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Do the following Remove the service cover a with screw b Remove the p...

Page 16: ...ists of the following stages 1 Checking for leaks in the refrigerant piping 2 Performing vacuum drying to remove all moisture air or nitrogen from the refrigerant piping If there is a possibility of m...

Page 17: ...it is factory charged with refrigerant but in some cases the following might be necessary What When Charging additional refrigerant When the total liquid piping length is more than specified see later...

Page 18: ...ak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating dev...

Page 19: ...ins fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When charging refrigerant always use protective gloves and safety glasses CAU...

Page 20: ...frigerant charge in the system expressed as tonnes CO2 equivalent is used to determine the maintenance intervals Follow the applicable legislation Formula to calculate the greenhouse gas emissions GWP...

Page 21: ...ble legislation Interconnection cables Minimum cable section of 2 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 32 A 16 A 20 A Earth leakage circuit breaker Must comply with applicabl...

Page 22: ...e frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tub...

Page 23: ...eat up the compressor oil to avoid oil shortage and compressor breakdown during startup NOTICE NEVER operate the unit without thermistors and or pressure sensors switches Burning of the compressor mig...

Page 24: ...vice cover to prevent electric shocks 3 Turn ON power for at least 6 hours before starting operation to protect the compressor 4 On the user interface set the unit to cooling operation mode 2 Start th...

Page 25: ...the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least once a year However applicable legislation might...

Page 26: ...y for reuse recycling and recovery 11 1 Overview Disposal Typical workflow Disposing of the system typically consists of the following stages 1 Pumping down the system 2 Bringing the system to a speci...

Page 27: ...row of units A E a b c d e eB eD a b c d e eB eD A B C D E B HU HD H B 100 A B C 250 100 100 B E 100 1000 500 A B C E 250 150 150 1000 500 D 500 D E 500 1000 500 B D 100 500 B D E 1 2 1 HB HD HB HU 25...

Page 28: ...e upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bottom plate B1 B2 B1 If there is no danger of drainage dripping and freezing between the upper and lower units...

Page 29: ...ctive devices S1PH S1PLand Q1E 3 Refer to the combination table and the option manual for how to connect the wiring to X6A X28A and X77A 4 Colours BLK black RED red BLU blue WHT white GRN green 4 Lege...

Page 30: ...licable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a cer...

Page 31: ......

Page 32: ...4P486047 1 2017 04 Copyright 2017 Daikin...

Reviews: