19
|
Configuration
Installer and user reference guide
136
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
When you want to use the automatic leak detection function you have to activate
this setting. By activating setting [2‑86], the automatic leak detection will be
executed depending on the defined value setting. The timing for the next
automatic refrigerant leak detection is subject to setting [2‑85]. The automatic leak
detection will be executed in [2‑85] days.
Each time when the automatic leak detection function was executed the system
will stay idle until it is restarted by manual thermo ON request or by next
scheduled action.
[2‑86]
Description
0 (default)
No leak detection planned.
1
Leak detection planned once in [2‑85] days.
2
Leak detection planned every [2‑85] days.
[2‑88]
Gathering detailed refrigerant information during test run for leak detection
functionality. For more details, see
[2‑88]
Description
0 (default)
Activated.
1
Deactivated.
19.2.9 To connect the PC configurator to the outdoor unit
X27A
a
b
c
2
3
4
5
H J
ST
X27A
A1P
a
PC
b
Cable (EKPCCAB*)
c
Outdoor unit main PCB
19.3 Energy saving and optimum operation
This heat pump system is equipped with advanced energy saving functionality.
Depending on the priority, emphasises can be put on energy saving or comfort
level. Several parameters can be selected, resulting in the optimal balance
between energy consumption and comfort for the particular application.
Several patterns are available and explained below. Modify the parameters to the
needs of your building and to realize the best balance between energy
consumption and comfort.
Summary of Contents for RYYQ8U7Y1B
Page 174: ......
Page 175: ......
Page 176: ...4P546228 1C 2021 11 Copyright 2018 Daikin Verantwortung f r Energie und Umwelt...