6 Installation
Installer and user reference guide
25
RXYSQ4~Y1B
VRV IV-S system air conditioner
4P404676-1A – 2016.03
e
d
F1/F2
(16 V)
F1/F2
(16 V)
220-240 V
1~ 50 Hz
c
a
Y1
V1
b
220-240 V
1~ 50 Hz
380-415 V
3N~ 50 Hz
a
Main switch
b
Earth connection
c
Power supply wiring (including earth) (sheathed cable)
F1/F2
Transmission wiring (sheathed cable)
V1
Outdoor unit (RXYSQ4~6_V1)
Y1
Outdoor unit (RXYSQ4~6_Y1)
d
Indoor unit
e
User interface
Power supply wiring and transmission wiring
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wiring should always be at
least 50 mm.
NOTICE
▪ Be sure to keep the power line and transmission line
apart from each other. Transmission wiring and power
supply wiring may cross, but may not run parallel.
▪ Transmission wiring and power supply wiring may not
touch internal piping (except the inverter PCB cooling
pipe) in order to avoid wire damage due to high
temperature piping.
▪ Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
The transmission wiring outside the unit should be wrapped and
routed together with the field piping.
Branches
Maximum number of branches
for unit-to-unit cabling
9
Transmission wiring
Vinyl cords with 0.75 to 1.25 mm²
sheath or cables (2‑core wires)
Maximum wiring length
(= distance between outdoor and
furthest indoor unit)
300 m
Total wiring length
(= distance between outdoor and
all indoors)
600 m
If the total transmission wiring exceeds these limits, it may
result in communication error.
No branching is allowed after branching.
A
B
C
b2
b3
c1
c2
b1
a
A
Outdoor unit
B
Indoor unit
C
Central user interface (etc...)
a
Main line
b1, b2, b3
Branch lines
c1, c2
No branch is allowed after branch
6.8.2
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
All field wiring and components must be installed by a
licensed electrician and must comply with the applicable
legislation.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, shall be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
Install power cables at least 1 metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1 metre may not be sufficient.