
6 Installation
Installer and user reference guide
23
RXYSQ4~Y1B
VRV IV-S system air conditioner
4P404676-1A – 2016.03
NOTICE
Before starting charging procedures, check if the 7‑LEDs
display is as normal (see
"7.2.4 To access mode 1 or 2" on
), and there is no malfunction code on the user
interface of the indoor unit. If a malfunction code is
present, see
"11.3 Solving problems based on error
NOTICE
Make sure all connected indoor units are recognised
(setting [1‑5]).
NOTICE
Close the front panel before any refrigerant charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.
NOTICE
In case of maintenance and the system (outdoor unit+field
indoor units) does not contain any refrigerant any
more (e.g., after refrigerant reclaim operation), the unit has
to be charged with its original amount of refrigerant (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.
6.7.3
To determine the additional refrigerant
amount
INFORMATION
For final charge adjustment in a test laboratory, contact
your dealer.
Additional refrigerant to be charged=R (kg). R should be rounded off
in units of 0.1 kg.
R=[(X
1
×
Ø9.5
)×0.059+(X
2
×
Ø6.4
)×0.022]
X
1...2
=Total length (m) of liquid piping size at
Øa
INFORMATION
Piping length is considered the distance from the outdoor
unit to the farthest indoor unit.
When using metric piping, please take into account following table
concerning the weight factor to be allocated. It should be substituted
in the formula for R.
Inch piping
Metric piping
Size (Ø) (mm)
Weight factor
Size (Ø) (mm)
Weight factor
6.4
0.022
6
0.018
9.5
0.059
10
0.065
When selecting indoor unit, following table with connection ratio
limitation has to be respected. More detailed information can be
found in technical engineering data.
Used indoor
units
Total capacity
CR
(a)
Allowable capacity connection
ratio
VRV DX
RA DX
VRV DX
50~130%
50~130%
—
RA DX
80~130%
—
80~130%
(a)
CR=Connection ratio.
6.7.4
To charge refrigerant
To speed up the refrigerant charging process, it is in case of larger
systems recommended to first pre-charge a portion of refrigerant
through the liquid line before proceeding with the manual charging. It
can be skipped, but charging will take longer then.
Pre-charging refrigerant
Pre-charging can be done without compressor operation, by
connecting the refrigerant bottle to the service port of the liquid stop
valve.
1
Connect as shown. Make sure that all outdoor unit stop valves,
as well as valve A are closed.
p< p>
N2
C
b
c
e
a
g
f
d
A
B
a
Pressure reducing valve
b
Nitrogen
c
Weighing scales
d
Refrigerant R410A tank (siphon system)
e
Vacuum pump
f
Liquid line stop valve
g
Gas line stop valve
A
Valve A
B
Valve B
C
Valve C
2
Open valves C and B.
3
Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.
4
Do one of the following:
If
Then
The determined additional
refrigerant amount is
reached
Disconnect the manifold from
the liquid line.
You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.
Too much
refrigerant is
charged
Recover refrigerant.
Disconnect the manifold from
the liquid line.
You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.
The determined additional
refrigerant amount is
not
reached
yet
Disconnect the manifold from
the liquid line.
Continue with the "Charging
refrigerant (in manual
additional refrigerant charge
mode)" instructions.
Charging refrigerant (in manual additional refrigerant charge
mode)
The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the manual additional
refrigerant charge mode.
5
Connect as shown. Make sure valve A is closed.