5 Preparation
Installer and user reference guide
9
RXYSCQ4~6TMV1B
VRV IV-S system air conditioner
4P404224-1C – 2019.07
The VRV IV-S heat pump system can be combined with several
types of indoor units and is intended for R410A use only.
For an overview which units are available you can consult the
product catalogue for VRV IV-S.
An overview is given indicating the allowed combinations of indoor
units and outdoor units. Not all combinations are allowed. They are
subject to rules (combination between outdoor-indoor, combinations
between indoor units, etc.) mentioned in the technical engineering
data.
4.5.2
Possible combinations of indoor units
In general following type of indoor units can be connected to a VRV
IV-S heat pump system. The list is non-exhaustive and is depending
on both outdoor unit model and indoor unit model combinations.
▪ VRV direct expansion (DX) indoor units (air to air applications).
▪ SA/RA (Sky Air/Residential Air) direct expansion (DX) indoor units
(air to air applications). Further referred to as RA DX indoor units.
These indoor units require a BP box.
▪ AHU (air to air applications): EKEXV-kit+EKEQ-box are required,
depending on application.
▪ Aircurtain (air to air applications): CYV/CAV (Biddle) series,
depending on application.
INFORMATION
▪ Combination of VRV DX and RA DX indoor units is not
allowed.
▪ Combination of RA DX and AHU indoor units is not
allowed.
▪ Combination of RA DX and aircurtain indoor units is not
allowed.
4.5.3
Possible options for the outdoor unit
INFORMATION
Refer to the technical engineering data for the latest option
names.
Refrigerant branching kit
Description
Model name
Refnet header
KHRQ22M29H
Refnet joint
KHRQ22M20T
For the selection of the optimal branching kit, please refer to
"5.3.4 To select refrigerant branch kits" on page 13
External control adaptor (DTA104A61/62)
To instruct specific operation with an external input coming from a
central control the external control adaptor can be used. Instructions
(group or individual) can be instructed for low noise operation and
power consumption limitation operation.
The external control adapter has to be installed in the indoor unit.
PC configurator cable (EKPCCAB)
You can make several commissioning field settings through a
personal computer interface. For this option EKPCCAB is required
which is a dedicated cable to communicate with the outdoor unit.
The
user
interface
software
is
available
on
www.daikineurope.com/support-and-manuals/software-downloads/
5
Preparation
5.1
Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the electrical wiring
5.2
Preparing the installation site
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the
unit in and out of the site.
5.2.1
Installation site requirements of the
outdoor unit
INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Service space requirements. See the "Technical data"
chapter.
▪ Refrigerant
piping
requirements
(length,
height
difference). See further in this "Preparation" chapter.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
a
commercial
and
light
industrial
environment.
NOTICE
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc.
b
b
a
a
c
d
f e
(mm)
≥1500
≥1500
≥1500
≥1000
≥1000
≥1000
≥1000
≥1000
≥1000
e
a
Personal computer or radio
b
Fuse
c
Earth leakage protector
d
User interface
e
Indoor unit
f
Outdoor unit