• Outdoor Units • VRV HEAT PUMP • RXYHQ12-36P(8)
1
1
• VRV Systems • Outdoor Units
5
1
Specifications
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Capacity Control
~ 100
Safety devices
HPS
Fan motor driver overload protector
Over current relay
Inverter overload protector
PC board fuse
Standard
Accessories
Standard Accessories
Installation manual
Quantity
1
1
1
1
1
1
Standard Accessories
Operation manual
Quantity
1
1
1
1
1
1
Standard Accessories
Connection pipes
Quantity
4
4
4
4
4
4
Notes
Nominal cooling capacities are based on : indoor temperature : 27×CDB, 19×CWB, outdoor temperature : 35×CDB,
equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20×CDB, outdoor temperature : 7×CDB, 6×CWB,
equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant
charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent
systems, each containing less th
1-3 ELECTRICAL SPECIFICATIONS
(50HZ)
RXYHQ12P8W1B
RXYHQ16P8W1B
RXYHQ18P8W1B
RXYHQ20P8W1B
RXYHQ22P8W1B
RXYHQ24P8W1B
Power Supply
Name
W1
Phase
3N~
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Current
Nominal
running current
(RLA)
Cooling
A
19.1
15.0
18.8
26.6
30.4
22.5
Heating
A
12.9
16.4
19.3
21.1
24.0
24.6
Starting current (MSC)
A
75
4
78
79
88
7
Z-max
Text
0.27
-
0.27
0.27
0.25
-
Minimum Ssc value
kVa
1,114
2,436
2,146
2,332
2,042
3,654
Minimum circuit amps
(MCA)
A
22.7
37.0
40.1
41.2
44.3
55.5
Maximum fuse amps (MFA) A
25
50
50
50
50
63
Full load amps (FLA)
A
1.2
1.4
1.6
1.9
2.1
2.1
Voltage range
Minimum
V
360
360
360
360
360
360
Maximum
V
440
440
440
440
440
440
Wiring
connections
For Power
Supply
Quantity
5
5
5
5
5
5
Remark
Earth wire include
For connection
with indoor
Quantity
2
2
2
2
2
2
Remark
F1-F2
Power Supply Intake
Both indoor and outdoor unit
1-2 TECHNICAL SPECIFICATIONS
RXYHQ26P8W1B
RXYHQ28P8W1B
RXYHQ30P8W1B
RXYHQ32P8W1B
RXYHQ34P8W1B
RXYHQ36P8W1B