Outline of Control (Indoor Unit)
SiUS331708EA
85
Functions and Control
6.16 Fan Control (Heater Residual) (FXTQ-TA Models)
Outline
If the indoor heater turned OFF from ON during heating operation, the fan will keep operating for
further period of time in order to cool the heater.
Detail
∗
1. When the heater is ON, the airflow rate of the fan will be whichever is the largest between the
CFM dictated by the heater's own capacity, or the fan tap CFM determined by other controls.
∗
2. Fan residual operation will continue, even if the indoor unit is turned off with the remote
controller operation button.
6.17 Interlocked with External Equipment (FXTQ-TA and
CXTQ-TA Models)
6.17.1 Air Purifier (UV lamp)
When an air purifier is connected onsite, the fan is operated with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-AIR CLEANER terminal on the PCB.
∗
2. Refer to page 106 for field setting 14(24)-4.
6.17.2 Humidifier
When a humidifier is connected onsite, the fan operates with the airflow rate set of the remote
controller or with the H tap.
∗
1. External input ON is an input signal to the X1M-HUMIDIFIER terminal on the PCB.
∗
2. Refer to page 106 for field setting 14(24)-4.
Note:
This control is not applicable to the humidifier connected to the wiring adaptor, but to the humidifier
connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB.
•
Heater turned OFF from ON
OR
•
Heater ON
•
Time up (
∗
2)
Residual OFF
Residual ON
Fan (
∗
1)
ENTRY/
90 sec. timer starts.
&
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
•
Remote control operation
(including thermostat OFF)
•
External input: ON (
∗
1)
&
&
•
Remote control operation: ON
(including thermostat OFF)
•
When the external input
changes from ON to OFF.
•
Remote control operation: ON
(including thermostat OFF)
•
External input: ON (
∗
1)
Fan X tap operation
(X tap is selectable by field setting. (
∗
2))
Fan residual operation for 30 seconds
(The fan airflow rate is set with the X tap.)
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...