SiUS331708EA
Check
Service Diagnosis
270
5.12 Master Unit Centralized Connector Setting Table
The master unit centralized setting connector (CN1/X1A) is installed at the factory.
•
To independently use a single unit of the intelligent Touch Controller or a single unit of the
centralized remote controller, do not dismount the master unit centralized setting connector (i.e.,
use the connector with the factory setting unchanged).
•
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been installed at the factory. Insert the connector,
which is attached to the casing of the master unit, in the PCB (CN1/X1A).
(Independent-use connector: Master unit centralized setting connector)
•
To use two or more centralized controllers in combination, make settings according to the table
shown below.
Notes:
∗
1
The intelligent Touch Controller and the schedule timer are not available for combined use.
∗
2
The intelligent Touch Controller, centralized remote controller, and the unified ON/OFF controller have been set to "Provided with the master
unit centralized setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit centralized setting
connector" at the factory, which is attached to the casing of the master unit.
CHECK 13
Centralized controller connection pattern
Setting of master unit centralized setting connector (
∗
2)
× (
∗
1)
1 unit
1 unit
× (
∗
1)
Provided
Not provided
× (
∗
1)
× (
∗
1)
1 unit
Not provided
1 unit
Not provided
1 unit
Not provided
1 unit
Provided
intelligent
Touch
Controller
Centralized
remote
controller
Unified
ON/OFF
controller
Schedule
timer
intelligent
Touch
Controller
Centralized
remote
controller
Unified
ON/OFF
controller
Schedule
timer
Only a
single unit:
"Provided",
Others: "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
1 to 16
units
1 to 16
units
1 to 8
units
1 to 4
units
1 to 2
units
1 to 2
units
Pattern
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...