Troubleshooting by Error Code
SiUS331708EA
249
Service Diagnosis
4.67 Address Duplication, Poor Setting
Error Code
MC
Applicable
Models
Centralized controller
intelligent Touch Controller
Schedule timer
Method of Error
Detection
DIII-NET communication data is used to detect the error.
Error Decision
Conditions
Multiple centralized controllers or intelligent Touch Controllers are connected, and the controllers
are both set as master centralized controllers or slave centralized controllers.
Two schedule timers are connected.
Supposed
Causes
Centralized controller address duplication