SiUS331708EA
Test Operation
Field Settings and Test Operation
136
3.5
Error Codes and Corresponding Measures
Please check the remote controller connected to the indoor unit for verification.
Error code
Description
Solution
E3
High pressure switch activated (S1PH)
Check the stop valve or (field) piping abnormality
or the airflow on the air cooling heat exchanger.
· Too much refrigerant charged
· Stop valve closed
· Check the amount of refrigerant and recharge
the unit.
· Open the stop valve.
Stop valve closed (liquid).
Open the liquid stop valve.
· Too much refrigerant charged
· Stop valve closed
· Check the amount of refrigerant and recharge
the unit.
· Open the stop valve.
E4
Defective low pressure:
· Stop valve closed
· Refrigerant undercharged
· Defective indoor unit
· Open the stop valve.
· Check the amount of refrigerant and recharge
the unit.
· Check the user interface display.
· Check the transmission wiring between the
indoor and outdoor units.
E9
Defective electronic expansion valve
(Subcooling) (RXSQ60TAVJU: Y3E)
Check the connection of the PCB or the actuator.
Defective electronic expansion valve (Main)
(Y1E)
Check the connection of the PCB or the actuator.
F3
Discharge pipe temperature too high:
· Stop valve closed
· Refrigerant undercharged
· Open the stop valve.
· Check the amount of refrigerant and recharge
the unit.
H9
Defective outdoor air thermistor (R1T)
Check the connection of the PCB or the actuator.
J3
Defective discharge pipe thermistor (R2T):
Tripping
Check the connection of the PCB or the actuator.
Defective discharge pipe thermistor (R2T):
Short circuit
Check the connection of the PCB or the actuator.
J5
Defective suction pipe thermistor
(R3T and R5T): Tripping
Check the connection of the PCB or the actuator.
J6
Defective outdoor heat exchanger deicer
thermistor (R4T)
Check the connection of the PCB or the actuator.
J7
Defective heat exchanger liquid pipe thermistor
(R7T)
Check the connection of the PCB or the actuator.
J9
Defective subcooling heat exchanger gas pipe
thermistor (R6T: RXSQ60TAVJU only)
Check the connection of the PCB or the actuator.
JA
Defective high pressure sensor (S1NPH):
Tripping
Check the connection of the PCB or the actuator.
Defective high pressure sensor (S1NPH):
Short circuit
Check the connection of the PCB or the actuator.
JC
Defective low pressure sensor (S1NPL):
Tripping
Check the connection of the PCB or the actuator.
Defective low pressure sensor (S1NPL):
Short circuit
Check the connection of the PCB or the actuator.
P1
Inverter unbalanced power supply voltage
Check if the power supply meets the
specifications.
U2
Inverter insufficient voltage
Check if the power supply meets the
specifications.
Inverter power supply phase missing
Check if the power supply meets the
specifications.
U3
System test operation not yet executed (Test
operation cannot be executed.)
Execute system test operation.
U4
Q1/Q2 or indoor-outdoor units wiring error
Check (Q1/Q2) wiring.
Q1/Q2 or indoor-outdoor units wiring error
Check (Q1/Q2) wiring.
System test operation ends abnormally.
Re-execute the test operation.
U9
System mismatch
Mismatched indoor unit models used (R-410A,
R-407C, RA, Hydrobox, etc.).
Defective indoor unit
Check if there are any other defective indoor
units and verify if the indoor unit combination
meets requirements.
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...