Test Operation
SiUS331708EA
131
Field Settings and Test Operation
3. Test Operation
Follow the following procedure to conduct the initial test operation after installation.
3.1
Check Work Prior to Turning Power Supply ON
3.2
Turn Power ON
Check on refrigerant piping /
insulation material
Check on amount of refrigerant
charge
Check the below items.
•
Power wiring
•
Control transmission wiring
between units
•
Earth wire
•
Is the power supply appropriate?
•
Have you finished a ductwork to drain?
•
Have you detach transport fitting?
•
Is the wiring performed as specified?
•
Are the designated wires used?
•
Is the grounding work completed?
Use a 500 V Megger tester to measure the insulation.
Do not use a Megger tester for low voltage circuits.
•
Are the setscrews of wiring not loose?
•
Is the electrical component box covered with an insulation cover
completely?
•
Is refrigerant charged up to the specified amount?
If insufficient, charge the refrigerant from the service port of stop
valve on the liquid side with outdoor unit in stop mode after turning
power ON.
•
Has the amount of refrigerant charge been recorded on “Record
Chart of Additional Refrigerant Charge Amount”?
•
Is pipe size proper? (The design pressure of this product is 4.0
MPa (580 psi).)
•
Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes
water leak.)
•
Are respective stop valves on liquid and gas line securely open?
Turn outdoor unit power ON.
Turn indoor unit power ON.
•
Be sure to turn the power ON 6 hours before starting operation to
protect compressors.
•
Close outside panels of the outdoor unit.
Carry out field setting on
outdoor PCB
Summary of Contents for RXSQ24TAVJU
Page 1: ...Service Manual SiUS331708EA RXSQ24 36 48 60TAVJU Heat Pump 60 Hz...
Page 290: ...Wiring Diagrams SiUS331708EA 277 Appendix RXSQ48TAVJU 3D109546A...
Page 291: ...SiUS331708EA Wiring Diagrams Appendix 278 RXSQ60TAVJU 3D109547A...
Page 295: ...SiUS331708EA Wiring Diagrams Appendix 282 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 298: ...Wiring Diagrams SiUS331708EA 285 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 300: ...Wiring Diagrams SiUS331708EA 287 Appendix FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU 3D110467B...
Page 301: ...SiUS331708EA Wiring Diagrams Appendix 288 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 302: ...Wiring Diagrams SiUS331708EA 289 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 303: ...SiUS331708EA Wiring Diagrams Appendix 290 FXAQ07 09 12 18 24PVJU 3D075354C...
Page 309: ...SiUS331708EA Wiring Diagrams Appendix 296 VAM1200GVJU 3D073270D...